Loading…

Variable Name: CAL_Cal_Mode

Variable ID: 0x4032

Variable Label: Calbr Mode

Variable Help: This variable shows the state of the positioner during calibration. Each value of Calibrate corresponds to a specific stage in the calibration process: Calibrate=0, Normal operation, calibration OFF, position control enabled; Calibrate=1, Automatically calibrate stroke; Calibrate=2, Automatically calibrate actuator pressure sensors; Calibrate=3, acquire command counts with loop current at 0%; Calibrate=4, command counts with loop current at 100%; Calibrate=5, Moving valve to closed position, get Stem position at 0%; Calibrate=6, moving valve to open position, get stem position at 100%; Calibrate=7, Calibrating supply sensor; Calibrate = 8, Calibrating Actuator Sensor, closing valve; Calibrate=9, Calibrating Actuator sensor, opening valve; Calibrate = 11, quick-cal button has been pressed; Calibrate=12,Error occurred during Calibration.

Variable Handling: R/W

Variable Class: Dynamic | InputBlock

Variable Size: 1

Variable DataType: Unsigned

Variable Display Format: |en|3d

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
224 419A Read_Calibration_cmd
226 419C Read_Cal_Loop_cmd

Variable Write Command List

Command Number Command ID Command Name
225 419B Write_Calibration_cmd
227 419D Write_Cal_Loop_cmd