Variable Name: CAL_Cal_Mode
Variable ID: 0x4032
Variable Label: Calbr Mode
Variable Help: This variable shows the state of the positioner during calibration. Each value of Calibrate corresponds to a specific stage in the calibration process: Calibrate=0, Normal operation, calibration OFF, position control enabled; Calibrate=1, Automatically calibrate stroke; Calibrate=2, Automatically calibrate actuator pressure sensors; Calibrate=3, acquire command counts with loop current at 0%; Calibrate=4, command counts with loop current at 100%; Calibrate=5, Moving valve to closed position, get Stem position at 0%; Calibrate=6, moving valve to open position, get stem position at 100%; Calibrate=7, Calibrating supply sensor; Calibrate = 8, Calibrating Actuator Sensor, closing valve; Calibrate=9, Calibrating Actuator sensor, opening valve; Calibrate = 11, quick-cal button has been pressed; Calibrate=12,Error occurred during Calibration.
Variable Handling: R/W
Variable Class: Dynamic | InputBlock
Variable Size: 1
Variable DataType: Unsigned
Variable Display Format: |en|3d
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
224 | 419A | Read_Calibration_cmd |
226 | 419C | Read_Cal_Loop_cmd |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
225 | 419B | Write_Calibration_cmd |
227 | 419D | Write_Cal_Loop_cmd |