Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 PV Analog Channel Saturated
0x0008 PV Analog Channel Fixed
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
128 42B1 Read_Positioner_Information
130 42B2 Read_Gain_Data
132 42B4 Read_Command_Position_Data
136 42B6 Read_License_Mode_and_ESN
138 42B7 Read_Configuration_Data
140 42B9 Read_Valve_Actuator_Data
142 42BB Read_User_Selectable_Units
154 42BD Read_Pilot_Response_Data
156 42BF Read_Valve_Travel_Cycle_Data
162 42C1 Read_Pilot_Travel_Cycle_Data
168 42C3 Read_Temperature_Data
172 42C4 Read_Position_Limit_Data
174 42C6 Read_Status_Data
175 42C7 Read_PST_Results_Data
176 42C8 Read_StatusMask_Data
178 42CA Read_LocalInterface_Data
182 42CC Read_Time_Date
184 42CE Read_Calibration_Time_Date
186 42D0 Read_Piezo_Data
200 42D3 Read_Misc_cmd
210 42D5 Read_Signature_Number
212 42D7 Read_Signature_Config_Data
236 42D9 Read_Event_Timeline_Configuration
238 42DB Read_Event_History
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
9 00DD read_device_variables_and_status
7 00DB read_loop_configuration
8 00DC read_dynamic_variable_classification
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
20 00DE read_long_tag
33 1054 read_device_variables
48 1043 read_additional_device_status
105 1063 read_burst_mode_configuration
50 1052 read_device_variable_assignments

Variable Write Command List

None