Loading…

Variable Name: CO_FailsafeMode_1

Variable ID: 0x406E

Variable Label: Failure mode

Variable Help: Defines which current the output assumes in the case of an error. 'Min.': < 3.6mA 'Max.': > 21.95mA 'Last valid value': Last valid value before occurrence of the error. 'Actual value': Output current is equal to the measured value; error is ignored. 'Defined value': User defined value.

Variable Handling: R/W

Variable Class: Device

Variable Size: 2

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x80CC Min.
0x80C2 Max.
0x80A0 Last valid value
0x8016 Actual value
0x804D Defined value

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
173 469E read_index_parameter_173

Variable Write Command List

Command Number Command ID Command Name
178 469C write_index_parameter_178