Variable Name: DS_ActualDiagnostics1NE107_1
Variable ID: 0x4073
Variable Label: DS_ActualDiagnostics1NE107_1
Variable Help:
Variable Handling: R
Variable Class: Dynamic
Variable Size: 4
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | OK |
0x10029 | 041-Sensor interrupted |
0x1002A | 042-Sensor corroded |
0x1002B | 043-Short circuit |
0x1002F | 047-Sensor limit reached-Sensor 1 |
0x3002F | 047-Sensor limit reached-Device temperature |
0xE002F | 047-Sensor limit reached-Sensor RJ |
0x10091 | 145-Compensation refrence point-Sensor 1 |
0x00C9 | 201-Electronics faulty |
0x100C9 | 201-Electronics faulty-Sensor 1 |
0x300C9 | 201-Electronics faulty-Device temperature |
0xE00C9 | 201-Electronics faulty-Sensor RJ |
0x300DD | 221-Reference sensor defective |
0xE00DD | 221-Reference sensor defective-Sensor RJ |
0x0191 | 401-Factory reset active |
0x0192 | 402-Initialization active |
0x10192 | 402-Initialization active-Sensor 1 |
0x30192 | 402-Initialization active-Device temperature |
0xE0192 | 402-Initialization active-Sensor RJ |
0x019A | 410-Data transfer failed |
0x019B | 411-Up-/download active |
0x101B3 | 435-Linearization faulty-Sensor 1 |
0x301B3 | 435-Linearization faulty |
0xE01B3 | 435-Linearization faulty-Sensor RJ |
0x101E5 | 485-Process variable simulation active-Sensor 1 |
0x301E5 | 485-Process variable simulation active-Device temperature |
0xB01EB | 491-Output simulation-Current output |
0x01EF | 495-Diagnostic event simulation active |
0x10213 | 531-Factory adjustment missing-Sensor 1 |
0xB0213 | 531-Factory adjustment missing-Current output |
0x0219 | 537-Configuration |
0x10219 | 537-Configuration-Sensor 1 |
0xB0219 | 537-Configuration-Current output |
0x10246 | 582-Sensor diagnostics TC deactivated |
0x0321 | 801-Supply voltage too low |
0x0339 | 825-Operating temperature |
0xB034C | 844-Process value out of specification |
0x11029 | S041-Sensor interrupted |
0x1102A | S042-Sensor corroded |
0x1102B | S043-Short circuit |
0x1102F | S047-Sensor limit reached-Sensor 1 |
0x3102F | S047-Sensor limit reached-Device temperature |
0xE102F | S047-Sensor limit reached-Sensor RJ |
0x11091 | S145-Compensation refrence point-Sensor 1 |
0x10C9 | S201-Electronics faulty |
0x110C9 | S201-Electronics faulty-Sensor 1 |
0x310C9 | S201-Electronics faulty-Device temperature |
0xE10C9 | S201-Electronics faulty-Sensor RJ |
0x310DD | S221-Reference sensor defective |
0xE10DD | S221-Reference sensor defective-Sensor RJ |
0x1191 | S401-Factory reset active |
0x1192 | S402-Initialization active |
0x11192 | S402-Initialization active-Sensor 1 |
0x31192 | S402-Initialization active-Device temperature |
0xE1192 | S402-Initialization active-Sensor RJ |
0x119A | S410-Data transfer failed |
0x119B | S411-Up-/download active |
0x111B3 | S435-Linearization faulty-Sensor 1 |
0x311B3 | S435-Linearization faulty |
0xE11B3 | S435-Linearization faulty-Sensor RJ |
0x111E5 | S485-Process variable simulation active-Sensor 1 |
0x311E5 | S485-Process variable simulation active-Device temperature |
0xB11EB | S491-Output simulation-Current output |
0x11EF | S495-Diagnostic event simulation active |
0x11213 | S531-Factory adjustment missing-Sensor 1 |
0xB1213 | S531-Factory adjustment missing-Current output |
0x1219 | S537-Configuration |
0x11219 | S537-Configuration-Sensor 1 |
0xB1219 | S537-Configuration-Current output |
0x11246 | S582-Sensor diagnostics TC deactivated |
0x1321 | S801-Supply voltage too low |
0x1339 | S825-Operating temperature |
0xB134C | S844-Process value out of specification |
0x12029 | C041-Sensor interrupted |
0x1202A | C042-Sensor corroded |
0x1202B | C043-Short circuit |
0x1202F | C047-Sensor limit reached-Sensor 1 |
0x3202F | C047-Sensor limit reached-Device temperature |
0xE202F | C047-Sensor limit reached-Sensor RJ |
0x12091 | C145-Compensation refrence point-Sensor 1 |
0x20C9 | C201-Electronics faulty |
0x120C9 | C201-Electronics faulty-Sensor 1 |
0x320C9 | C201-Electronics faulty-Device temperature |
0xE20C9 | C201-Electronics faulty-Sensor RJ |
0x320DD | C221-Reference sensor defective |
0xE20DD | C221-Reference sensor defective-Sensor RJ |
0x2191 | C401-Factory reset active |
0x2192 | C402-Initialization active |
0x12192 | C402-Initialization active-Sensor 1 |
0x32192 | C402-Initialization active-Device temperature |
0xE2192 | C402-Initialization active-Sensor RJ |
0x219A | C410-Data transfer failed |
0x219B | C411-Up-/download active |
0x121B3 | C435-Linearization faulty-Sensor 1 |
0x321B3 | C435-Linearization faulty |
0xE21B3 | C435-Linearization faulty-Sensor RJ |
0x121E5 | C485-Process variable simulation active-Sensor 1 |
0x321E5 | C485-Process variable simulation active-Device temperature |
0xB21EB | C491-Output simulation-Current output |
0x21EF | C495-Diagnostic event simulation active |
0x12213 | C531-Factory adjustment missing-Sensor 1 |
0xB2213 | C531-Factory adjustment missing-Current output |
0x2219 | C537-Configuration |
0x12219 | C537-Configuration-Sensor 1 |
0xB2219 | C537-Configuration-Current output |
0x12246 | C582-Sensor diagnostics TC deactivated |
0x2321 | C801-Supply voltage too low |
0x2339 | C825-Operating temperature |
0xB234C | C844-Process value out of specification |
0x13029 | M041-Sensor interrupted |
0x1302A | M042-Sensor corroded |
0x1302B | M043-Short circuit |
0x1302F | M047-Sensor limit reached-Sensor 1 |
0x3302F | M047-Sensor limit reached-Device temperature |
0xE302F | M047-Sensor limit reached-Sensor RJ |
0x13091 | M145-Compensation refrence point-Sensor 1 |
0x30C9 | M201-Electronics faulty |
0x130C9 | M201-Electronics faulty-Sensor 1 |
0x330C9 | M201-Electronics faulty-Device temperature |
0xE30C9 | M201-Electronics faulty-Sensor RJ |
0x330DD | M221-Reference sensor defective |
0xE30DD | M221-Reference sensor defective-Sensor RJ |
0x3191 | M401-Factory reset active |
0x3192 | M402-Initialization active |
0x13192 | M402-Initialization active-Sensor 1 |
0x33192 | M402-Initialization active-Device temperature |
0xE3192 | M402-Initialization active-Sensor RJ |
0x319A | M410-Data transfer failed |
0x319B | M411-Up-/download active |
0x131B3 | M435-Linearization faulty-Sensor 1 |
0x331B3 | M435-Linearization faulty |
0xE31B3 | M435-Linearization faulty-Sensor RJ |
0x131E5 | M485-Process variable simulation active-Sensor 1 |
0x331E5 | M485-Process variable simulation active-Device temperature |
0xB31EB | M491-Output simulation-Current output |
0x31EF | M495-Diagnostic event simulation active |
0x13213 | M531-Factory adjustment missing-Sensor 1 |
0xB3213 | M531-Factory adjustment missing-Current output |
0x3219 | M537-Configuration |
0x13219 | M537-Configuration-Sensor 1 |
0xB3219 | M537-Configuration-Current output |
0x13246 | M582-Sensor diagnostics TC deactivated |
0x3321 | M801-Supply voltage too low |
0x3339 | M825-Operating temperature |
0xB334C | M844-Process value out of specification |
0x14029 | F041-Sensor interrupted |
0x1402A | F042-Sensor corroded |
0x1402B | F043-Short circuit |
0x1402F | F047-Sensor limit reached-Sensor 1 |
0x3402F | F047-Sensor limit reached-Device temperature |
0xE402F | F047-Sensor limit reached-Sensor RJ |
0x14091 | F145-Compensation refrence point-Sensor 1 |
0x40C9 | F201-Electronics faulty |
0x140C9 | F201-Electronics faulty-Sensor 1 |
0x340C9 | F201-Electronics faulty-Device temperature |
0xE40C9 | F201-Electronics faulty-Sensor RJ |
0x340DD | F221-Reference sensor defective |
0xE40DD | F221-Reference sensor defective-Sensor RJ |
0x4191 | F401-Factory reset active |
0x4192 | F402-Initialization active |
0x14192 | F402-Initialization active-Sensor 1 |
0x34192 | F402-Initialization active-Device temperature |
0xE4192 | F402-Initialization active-Sensor RJ |
0x419A | F410-Data transfer failed |
0x419B | F411-Up-/download active |
0x141B3 | F435-Linearization faulty-Sensor 1 |
0x341B3 | F435-Linearization faulty |
0xE41B3 | F435-Linearization faulty-Sensor RJ |
0x141E5 | F485-Process variable simulation active-Sensor 1 |
0x341E5 | F485-Process variable simulation active-Device temperature |
0xB41EB | F491-Output simulation-Current output |
0x41EF | F495-Diagnostic event simulation active |
0x14213 | F531-Factory adjustment missing-Sensor 1 |
0xB4213 | F531-Factory adjustment missing-Current output |
0x4219 | F537-Configuration |
0x14219 | F537-Configuration-Sensor 1 |
0xB4219 | F537-Configuration-Current output |
0x14246 | F582-Sensor diagnostics TC deactivated |
0x4321 | F801-Supply voltage too low |
0x4339 | F825-Operating temperature |
0xB434C | F844-Process value out of specification |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
168 | 41B0 | ReadAdvancedDiagnostics |
Variable Write Command List
None