Loading…
Loading…
Variable Name: CO_TauDamping_1
Variable ID: 0x407B
Variable Label: Damping current output
Variable Help: Enter time constant (PT1 element) to set the reaction time of the output signal to fluctuations in the measured value caused by process conditions. Additional information: - The smaller the time constant the faster the output reacts to fluctuations in the measured value. - If the time constant is 0, damping is deactivated.
Variable Handling: R/W
Variable Class: Device
Variable Size: 4
Variable DataType: Float
Variable Display Format: |en|.1f
Variable Edit Format: |en|.1f
Variable Unit:
Variable Max: 999.9
Variable Min: 0
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
173 | 42E8 | read_index_parameter_173 |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
178 | 42E6 | write_index_parameter_178 |