Variable Name: device_specific_status_16
Variable ID: 0x1033
Variable Label: Status Group 16
Variable Help: Field Device Specific Status Byte 17- Data that has Field Device status information relating to: failures / warnings / status of process's.
Variable Handling: R
Variable Class: Dynamic | Diagnostic | Device
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0002 | M503 Zero adjustment -> Remedy information: 1. Check measuring range 2. Check position adjustment |
0x0004 | F801 Supply voltage too low -> Remedy information: Increase supply voltage |
0x0008 | S802 Supply voltage too high -> Remedy information: Decrease supply voltage |
0x0010 | 822 Sensor temperature out of range -> Remedy information: 1. Check process temperature 2. Check ambient temperature |
0x0020 | 841 Operating range -> Remedy information: 1. Check the process pressure 2. Check the sensor range |
0x0080 | F102 Sensor incompatible error -> Remedy information: 1. Restart device 2. Contact service |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
48 | 1043 | read_additional_device_status |
Variable Write Command List
None