Variable Name: vSnsrErrE9SincePowerOn
Variable ID: 0x4302
Variable Label: Sensor Error E9 since Power On
Variable Help:
Variable Handling: R
Variable Class: Dynamic | Diagnostic | Device
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Wrong sensor part number (sensor lock active) |
0x0002 | EC: Mandatory sensor test at startup failed; PIR7x00: Unknown Error |
0x0004 | EC: Reference electrode test failed; PIR7x00: Unknown Error |
0x0008 | EC: An error occurred during loading the sensor data; PIR7x00: Unknown Error |
0x0010 | EC: Communication error or timeout at sensor test; PIR7x00: P8000 cannot set range of PIR7x00, sensor init required |
0x0020 | EC: CRC error in EC specific EC sensor data; PIR7x00: Value is not equal string. |
0x0040 | EC: Unknown Error; PIR7x00: SIL Password is not set to the default value |
0x0080 | Unknown Error |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
205 | 42F9 | read_error_history |
Variable Write Command List
None