Loading…
Loading…
Variable Name: status1Value
Variable ID: 0x4060
Variable Label: Status1
Variable Help: Actuator status
Variable Handling: R
Variable Class: Dynamic | Diagnostic | Device
Variable Size: 4
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Close limit |
0x0002 | Open Limit |
0x0004 | Closing |
0x0008 | Opening |
0x0010 | ESD Active |
0x0020 | Selector remote |
0x0040 | Selector local |
0x0080 | Selector off |
0x0100 | Interlock OP active |
0x0200 | Interlock CL active |
0x0400 | Fail safe |
0x0800 | Reserved |
0x1000 | Reserved |
0x2000 | Reserved |
0x4000 | Reserved |
0x8000 | Reserved |
0x10000 | Monitor Relay |
0x20000 | Motion inhibit |
0x40000 | DIN1 |
0x80000 | DIN2 |
0x100000 | DIN3 |
0x200000 | DIN4 |
0x400000 | DIN5 |
0x800000 | DIN6 |
0x1000000 | Aux in open |
0x2000000 | Aux in close |
0x4000000 | Aux in stop |
0x8000000 | Aux in Bus-on |
0x10000000 | Hardwired active |
0x20000000 | Positioner active |
0x40000000 | Reserved |
0x80000000 | Reserved |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
None
Variable Write Command List
None