Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label:

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
130 4044 read_pulse_config
134 4047 read_totalizer_value
136 4049 read_flowtube_infomation
138 404B read_display_select
140 404D read_lfc_value
142 404F read_function_set
144 4051 read_hilow_alarm
146 4053 read_coefficient_value
148 4055 read_gravity_value
150 4057 read_fail_safe_mode
152 4059 read_noise_reduction_config
154 405B read_flow_directions
156 405D read_type_changes
158 405F free_check
159 4060 read_trim_repoprt
171 4069 read_bilingal
173 406B read_low_flow_cut_flag
175 406D read_zero_comp
177 406F read_memory_addr
178 4070 read_memory_data
180 4072 read_analog_pcent
184 4076 read_pulse_pcent
188 407A read_ex_mode
192 407E read_stout
196 4082 read_preset_device_id
198 4084 read_abnormal_detection
200 4086 read_excitation_config
202 4088 read_all_or_si
204 408A read_auto_zero_range
206 408C read_ex_value_range
208 408E read_low_flow_suppress
210 4090 read_burn_out_sim
212 4092 read_communication_mode
214 4094 read_de_word_len
217 4097 read_pulse_coef_value
224 409B read_iout_da_val
235 40CE MTG_read_static_data_setup
236 40D9 read_electrode_status_sense
238 40E5 read_df7ma
244 40E8 read_df49ma
248 40EC read_span1_bcd
250 40F0 read_pulse_weight_bcd
252 40F2 read_ex_local_conf
233 40F4 read_flow_units_original
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
16 00B8 read_final_assembly_number
48 0FCE read_additional_transmitter_status
110 1001 read_all_dynamic_variables

Variable Write Command List

None