Variable Name: xmtr_specific_status_1

Variable ID: 0x0FB6

Variable Label: ステータス グループ 2

Variable Help: HI<LO: High limit alarm value < Low limit alarm value. Set alarm value as Hi > Lo. Span over: Check the detector size. Set the span as the flow velocity becomes 10m/s or less. Pulse scale: Correct pulse scale. Set the pulse scale as the span frequency becomes between 0.0001Hz and 200Hz. If engineering unit of span is volumetric, apply the volumetric unit to the pulse scale. If engineering unit of span is mass, apply the mass unit to the pulse scale. Pulse width: Set the correct pulse width to become duty 70% or less. Or set duty 50% as pulse width.

Variable Handling: R

Variable Class: Dynamic | Diagnostic | Device

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0002 IN LOCAL MODE
0x0004 DO OUTPUT MODE
0x0008 PLS OUTPUT MODE
0x0010 AO OUTPUT MODE
0x0020 IN CALIB MODE
0x0040 NOT CALIBRATED
0x0080 EX OUTPUT MODE

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
48 0FCE read_additional_transmitter_status

Variable Write Command List