Variable Name: xmtr_specific_status_1
Variable ID: 0x0FB6
Variable Label: ステータス グループ 2
Variable Help: HI<LO: High limit alarm value < Low limit alarm value. Set alarm value as Hi > Lo. Span over: Check the detector size. Set the span as the flow velocity becomes 10m/s or less. Pulse scale: Correct pulse scale. Set the pulse scale as the span frequency becomes between 0.0001Hz and 200Hz. If engineering unit of span is volumetric, apply the volumetric unit to the pulse scale. If engineering unit of span is mass, apply the mass unit to the pulse scale. Pulse width: Set the correct pulse width to become duty 70% or less. Or set duty 50% as pulse width.
Variable Handling: R
Variable Class: Dynamic | Diagnostic | Device
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0002 | IN LOCAL MODE |
0x0004 | DO OUTPUT MODE |
0x0008 | PLS OUTPUT MODE |
0x0010 | AO OUTPUT MODE |
0x0020 | IN CALIB MODE |
0x0040 | NOT CALIBRATED |
0x0080 | EX OUTPUT MODE |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
48 | 0FCE | read_additional_transmitter_status |
Variable Write Command List
None