Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
176 402C read_pv_diagnosis_limits
190 4032 read_temperature_configuration
190 4032 read_temperature_configuration
191 4033 read_thermocouple_configuration
191 4033 read_thermocouple_configuration
202 4037 read_additional_temperature_parameters
202 4037 read_additional_temperature_parameters
171 403E READ_REVISIONS_AND_WRITE_PROTECT_STATE
192 4092 read_cvd_coefficients
192 4092 read_cvd_coefficients
192 4092 read_cvd_coefficients
192 4092 read_cvd_coefficients
192 4092 read_cvd_coefficients
238 40B0 read_drift_detection_parameters
174 40B2 read_current_out_alarm_configuration
230 40B4 read_maintenance_alarm_pulse_time
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
33 1054 read_device_variables
48 1043 read_additional_device_status
50 1052 read_device_variable_assignments
54 1057 read_device_variable_information

Variable Write Command List

None