Loading…

Command Name: x9800_cmd_rd_bitwise_status

Command ID: 4076

Command Number: 168

Command Operation: cmdOpRead

Command Transaction Count: 1

Command Transaction List

    Transaction Number: 0

    Transaction Request List

None

    Transaction Reply List

Item Type Flag Mast Int Float Variable ID
cmdDataReference cmdDataItemFlg_None 0 0 0 response_code
cmdDataReference cmdDataItemFlg_None 0 0 0 device_status
cmdDataWidth cmdDataItemFlg_None 128 0 0 x9800_bit_warm_up
cmdDataWidth cmdDataItemFlg_None 64 0 0 x9800_bit_man_oi_active
cmdDataWidth cmdDataItemFlg_None 32 0 0 x9800_bit_oi_cal_active
cmdDataWidth cmdDataItemFlg_None 16 0 0 x9800_bit_quick_alarm
cmdDataWidth cmdDataItemFlg_None 8 0 0 x9800_bit_tdsa_alarm
cmdDataWidth cmdDataItemFlg_None 4 0 0 x9800_bit_ir_alarm
cmdDataWidth cmdDataItemFlg_None 2 0 0 x9800_bit_uv_alarm
cmdDataWidth cmdDataItemFlg_None 1 0 0 x9800_bit_fire_status
cmdDataWidth cmdDataItemFlg_None 252 0 0 x9800_junk
cmdDataWidth cmdDataItemFlg_None 2 0 0 x9800_bit_ir_prealarm
cmdDataWidth cmdDataItemFlg_None 1 0 0 x9800_bit_uv_prealarm
cmdDataWidth cmdDataItemFlg_None 128 0 0 x9800_bit_temp_range_fault
cmdDataWidth cmdDataItemFlg_None 64 0 0 x9800_bit_ir_oi_cal_fault
cmdDataWidth cmdDataItemFlg_None 32 0 0 x9800_bit_uv_oi_cal_fault
cmdDataWidth cmdDataItemFlg_None 16 0 0 x9800_bit_auto_ir_oi_fault
cmdDataWidth cmdDataItemFlg_None 8 0 0 x9800_bit_auto_uv_oi_fault
cmdDataWidth cmdDataItemFlg_None 4 0 0 x9800_bit_man_ir_oi_fault
cmdDataWidth cmdDataItemFlg_None 2 0 0 x9800_bit_man_uv_oi_fault
cmdDataWidth cmdDataItemFlg_None 1 0 0 x9800_bit_fault_status
cmdDataWidth cmdDataItemFlg_None 192 0 0 x9800_junk
cmdDataWidth cmdDataItemFlg_None 32 0 0 x9800_bit_incompat_ver_fault
cmdDataWidth cmdDataItemFlg_None 16 0 0 x9800_bit_internal_comm_fault
cmdDataWidth cmdDataItemFlg_None 8 0 0 x9800_bit_hart_hdwr_fault
cmdDataWidth cmdDataItemFlg_None 4 0 0 x9800_bit_snsr_hdwr_fault
cmdDataWidth cmdDataItemFlg_None 2 0 0 x9800_bit_man_oi_start_fault
cmdDataWidth cmdDataItemFlg_None 1 0 0 x9800_bit_voltage_range_fault