0x1789001A |
flow_totalizer_block_help |
Flow Totalizer Block |
0x1789001B |
ft_view_1 |
Flow Transducer View 1 |
0x1789001C |
ft_view_1_help |
Flow Transducer View 1 |
0x1789001D |
ft_view_2 |
Flow Transducer View 2 |
0x1789001E |
ft_view_2_help |
Flow Transducer View 2 |
0x1789001F |
ft_view_3 |
Flow Transducer View 3 |
0x17890020 |
ft_view_3_help |
Flow Transducer View 3 |
0x17890021 |
ft_view_4 |
Flow Transducer View 4 |
0x17890022 |
ft_view_4_help |
Flow Transducer View 4 |
0x178E0000 |
section_6030 |
|
0x178E0001 |
reserved3_r_label |
Reserved |
0x178E0002 |
reserved3_r_help |
This field is reserved for future use |
0x178E0003 |
bkcal_outm_16_label |
BkCal Out 16 |
0x178E0004 |
bkcal_outm_16_help |
The output value and status provided to an upstream block for output tracking when the loop is broken or limited, as determined by the status bits. This information is used to provide bumpless transfer to closed loop control and to prevent windup under limited conditions when that becomes possible. |
0x178E0005 |
bkcal_outm__b64_label |
BkCal Out Binary 64 |
0x178E0006 |
bkcal_outm__b64_help |
The output value and status provided to an upstream block for output tracking when the loop is broken or limited, as determined by the status bits. This information is used to provide bumpless transfer to closed loop control and to prevent windup under limited conditions when that becomes possible. |
0x178E0007 |
__bkcal_outm_b64_value_label |
Values |
0x178E0008 |
__bkcal_outm_b64_value_help |
The 64 binary output values |
0x178E0009 |
__cas_inm_16_label |
Cas In 16 |
0x178E000A |
__cas_inm_16_help |
This parameter is the remote setpoint value, which must come from another Fieldbus block, or a DCS block through a defined link. |
0x178E000B |
__cas_inm_b64_label |
Cas In Binary 64 |
0x178E000C |
__cas_inm_b64_help |
This parameter is the remote setpoint value, which must come from another Fieldbus block, or a DCS block through a defined link. |
0x178E000D |
__cas_inm_b64_values_label |
Values |
0x178E000E |
__cas_inm_b64_values_help |
The 64 binary cascade input values |
0x178E000F |
channel_tag_elem |
Channel Tag Element |
0x178E0010 |
channel_tag_elem_help |
TAG of one I/O point to be mapped with the TAG in the I/O transducer block. Blank Tag means no association with I/O transducer block. |
0x178E0011 |
channel_tag_32a_label |
Channel Tag 64a |
0x178E0012 |
channel_tag_32a_help |
TAGs of the first 32 I/O points to be mapped with Tags in the I/O transducer block. Blank Tag means no association with I/O transducer block. The blocks MAP_MM_* parameter indicates if any Tags specified here are not found in a transducer block or if an output Tag is specified in more than one CHANNEL_TAG_* parameter. |
0x178E0013 |
channel_tag_32b_label |
Channel Tag 64b |
0x178E0014 |
channel_tag_32b_help |
TAGs of the second 32 I/O points to be mapped with Tags in the I/O transducer block. Blank Tag means no association with I/O transducer block. The blocks MAP_MM_* parameter indicates if any Tags specified here are not found in a transducer block or if an output Tag is specified in more than one CHANNEL_TAG_* parameter. |
0x178E0015 |
channel_tag_16_label |
Channel Tag 16 |
0x178E0016 |
channel_tag_16_help |
TAGs of the I/O point to be mapped with TAGs in the I/O transducer block. Blank Tag means no association with I/O transducer block. The blocks MAP_MM_* parameter indicates if any Tags specified here are not found in a transducer block or if an output Tag is specified in more than one CHANNEL_TAG_* parameter. |
0x178E0017 |
fstate_st_16_label |
FState State 16 |
0x178E0018 |
fstate_st_16_help |
Shows which points are in fault state. A 1 in bit N indicates that point N+1 is in fault state. |
0x178E0019 |
fstate_st_64_label |
FState State 64 |
0x178E001A |
fstate_st_64_help |
Shows which points are in fault state. A 1 in bit N indicates that point N+1 is in fault state. |
0x178E001B |
fstate_val_b64_label |
FState Binary Value 64 |
0x178E001C |
fstate_val_b64_help |
The preset binary values to use when failure occurs in CAS_IN_B64. Ignored for bit N if the corresponding \"Fault state to value n\" bit in the MO_OPTS_64 parameter is false. |
0x178E001D |
fstate_val_16_label |
FState Value 16 |
0x178E001E |
fstate_val_16_help |
The preset analog values to use when failure occurs in CAS_IN_16. Ignored for input \"n\" if the \"Fault state to value n\" bit (\"n-1\") in the MO_OPTS_16 parameter is false. |
0x178E001F |
map_mm_16_label |
Mapping Mismatch 16 |
0x178E0020 |
map_mm_16_help |
Shows which of 16 points are in Tag mismatching error. A \"1\" in bit \"n\" indicates that point \"n+1\" cannot be found in a transducer block. |
0x178E0021 |
map_mm_64_label |
Mapping Mismatch 64 |
0x178E0022 |
map_mm_64_help |
Shows which of 64 points are in Tag mismatching error. A \"1\" in bit \"n\" indicates that point \"n+1\" cannot be found in a transducer block. |
0x178E0023 |
mo_fstate_opts_16_label |
Multi Output FaultState Opts 16 |
0x178E0024 |
mo_fstate_opts_16_help |
The output action to take when fault occurs for each of 16 output values. (0: Freeze, 1: Go to preset fault state value in FSTATE_VAL_*) |
0x178E0025 |
mo_fstate_opts_64_label |
Multiple Output Options 64 |
0x178E0026 |
mo_fstate_opts_64_help |
Bitstring option for MBO-64 outputs. Utilizes corresponding value in FSTATE_VAL_B64 for fault state if set to 1. |
0x178E0027 |
force_enb_16_label |
Force Enable 16 |
0x178E0028 |
force_enb_16_help |
Controls the updating of each of the 16 analog points when the block is in AUTO mode. A value of 1 will stop the updating of the corresponding input/output point. |